vacon 500x parameters
7
799 Config USB Mode
Default: Disabled
Range: n/a
Level 2
This parameter allows you to select what kind of data you want to store in a flash memory device such as a
thumb drive or memory stick. For more information on using a flash memory device with the Vacon 500x,
see
Option
Description
0
Disabled
1
Parameter Store
2
Parameter Recall
3
Keeper Dump
801 Program Number
Default: 0
Range: 0 to 9999
Level 2, Macro
This parameter (Special Program Number) provides a way of enabling hidden functions in the drive and
storing parameters to the customer set.
Data Value
Special Function Configured
0
Standard program
1
Reset all parameters to factory default values (display = SETP).
2
Store customer parameter values (display = STOC).
3
Load customer parameter values (display = SETC).
4
Swap active parameters with customer stored settings.
Reset Total Run Time, parameter 108.
20
Enable writing of today’s time and today’s date parameter.
21
Store today’s time and today’s date parameter to RTC chip.
22
Abort time writing process.
30
Re-calibrate analog inputs (NOTE: no signal should be attached when performing
this).
40
Clear Keeper records.
50
Allow model-dependent parameters to be recalled by USB. (See
Note that data value 50 must be used to recall the following parameters via USB:
503
V/Hz Knee Freq
514
Motor RS
509
Rated Mtr Volt
515
Power Factor
510
Rated Mtr FLA
517
Single Phase
511
Rated Mtr RPM
Note also that the following parameters will never be recalled via USB:
490
Appl Macro
900
SIO Protocol
794
Drive Name
901
SIO Baud Rate
799
USB Config Mode
902
Comm Drop #
810
Language
916
Infrared Baud
811
Access Code
80
Disable Daylight Savings Time.
81
Enable Daylight Savings Time.
802 Start Options
Default: LS Lockout
Range: n/a
Level 2
The Start Options parameter configures the Line Start Lockout functionality of the drive. All data values
ending with “2” allow you to press the Enter key to store the customer speed reference value on the keypad.
You must press and hold the Enter key for two seconds to save the speed command. The following data
values may be assigned:
Data Value
Description
LS Lockout
(Line Start Lockout). If maintained contact run operators are used, they must be
opened and then re-closed for the drive to start after AC power is applied.
AutoStart
When AC power is applied, if a Run command is present through the terminal strip,
the drive will start.
LSL w/FLY This setting has both LS Lockout and Catch on the Fly enabled at the same time.
Auto w/FLY This setting has both Auto-Start and Catch on the Fly enabled at the same time.
LS Lockout2 (Line Start Lockout). If maintained contact run operators are used, they must be
opened and then re-closed for the drive to start after AC power is applied.
AutoStart2 When AC power is applied, if a Run command is present through the terminal strip,
the drive will start.
LSL w/FLY 2 This setting has both LS Lockout and Catch on the Fly enabled at the same
time.
Auto w/FLY2 This setting has both Auto-Start and Catch on the Fly enabled at the same time.
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......