Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
115
z
vacon troubleshooting
8
38
OP BRD Flt
Fault on
options board
0
Loss of communication
between option board and
drive.
Check connections.
Consult factory.
1
Could not identify option board
Consult factory.
2
The option board does not
match the last option board ID
that was active when the drive
was powered down.
Check and reconfigure
option board setup.
3
Option board ID is unsupported.
Consult factory.
4
Comm option board does not
have the proper daughter card
installed.
Consult factory.
5
Internal problem.
Consult factory.
6
Network communications
error.
Check connections and
setup.
7
Option board has been
removed.
Reconfigure.
39
Fan Loss
Loss of fan
control or
operation
0
There is a problem with the
heat sink fan.
Consult factory.
1
There is a problem with the
internal fan. This occurs only
on Size 4 and 5 models. All
other models display a fan
error warning.
Note that this is lack of fan
control, so the fan can be
spinning and this fault will still
occur. This can happen if the
fan is on and should not be, or if
the fan feedback signals are
obstructed from getting to the
control board.
Code
Fault Display
Description
Adv. Fault
Code
Explanation
Suggestions for
Recovery
Note: Shaded faults are auto-resettable, except where noted.
Table 1: Vacon 500x Fault Codes
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......