Tel. +358 (0)201 2121 • Fax +358 (0)201 212205
47
z
vacon operation and programming
5
5.7 Storing Data and Reflashing Using a Flash Memory Device
You can use a flash memory stick
(sometimes called a jump drive,
thumb drive, or flash drive) with the
USB port on the Vacon 500x. In this
way, software, program parameters
and Keeper data can be stored easily.
The file type for drive parameters is
the same as used by PDA-trAC Plus
with an extension of .tps. When
stored, the file is identified with the
name assigned in
.
Keeper data files have an extension of
.csv.
5.7.1 Storing Drive Parameters
1. Insert the memory stick in the
USB port.
2. Access
in Level 2
programming.
3. Select Par. Store and press the
Up button.
4. The display indicates the file
name that will be stored and
that you should press SHIFT to
proceed.
5. Follow the prompts on the
screen and when the memory
write is complete, the display
indicates that you should press the Down button to finish.
6. Pressing the Down button completes the store process. You will be returned to parameter 799, and the
value reverts to the default state of “disabled.”
7. Remove the memory stick. The parameter data is now stored.
5.7.2 Recalling Drive Parameters
1. Insert the memory stick in the USB port.
2. You will need to know the file name that you want to access, particularly if there is more than one .tps file
on the memory stick.
3. Access
parameter 799 (Config USB Mode)
in Level 2 programming.
4. Select Par. Recall and press the Up button.
5. The display indicates a file name, and that you should press SHIFT to proceed. Verify that the file name is
the one you wish to recall before pressing SHIFT.
6. After you have selected the file you want, press ENTER to continue.
7. Follow the prompts on the screen. When the recall is complete, the display indicates that you should press
the Down button to finish.
8. You will be returned to parameter 799, and the value reverts to the default state of “disabled.”
9. Remove the memory stick.
5.7.3 Storing Keeper Files
1. Insert the memory stick in the USB port.
2. Access
parameter 799 (Config USB Mode)
in Level 2 programming.
3. Select Keeper Dump and press the Up button.
4. The display indicates a file name that will be stored and that you should press SHIFT to proceed.
5. Follow the prompts on the screen. When the memory write is complete, the display indicates that you
should press the Down button to finish.
6. The file extension for a “keeper dump” file is .csv.
7. You will be returned to parameter 799, and the value reverts to the default state of “disabled.”
8. Remove the memory stick.
Vacon 500x Terminals and USB Port
USB Port
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......