32
4
Figure 8: Power Terminals on Higher-kW/HP Models
4.4.2 Typical Power Connections
starting on page 28 for input line requirements.
Note that when testing for a ground fault, do not short any motor lead (T1/U, T2/V, or T3/W) back to an input
phase (L1/R, L2/S, or L3/T).
It is necessary to provide fuses and a disconnect switch for the input AC line in accordance with all
applicable electrical codes. The Vacon 500x AC drive is able to withstand a 150% overload for 60 seconds
for heavy duty rating, and 120% overload for normal duty rating.
The fusing and input protection of the drive must always meet UL, NEC (National Electric Code), and CEC
(Canadian Electric Code) requirements. All fuse ratings included in
below are for reference only and
do not supersede code requirements. The recommended supplier is Bussman.
Model Number
Fuse Size
380 Vac
JJS
Fuse Size
460 Vac
JJS
0009 5
15
15
0012 5
20
20
0016 5
25
20
0023 5
40
35
0031 5
50
40
0037 5
60
50
0043 5
80
60
0061 5
100
80
0071 5
110
100
Table 5: Fuse Ratings