vacon 500x parameters
vacon
z
90
7
825 Flt Text #2
Default: User Flt 2
Range: n/a
Level 2
This parameter defines text to be displayed for fault message #2. All ASCII options are permitted.
850 PID Configure
Default: No PID
Range: n/a
Level 2
The PID Configure parameter determines what type of PID control is active in the drive.
PID can be active at all times, or activated using a digital input. If you select a digital input as the means to
enable PID control, remember to configure the parameter that sets the function of the digital input to enable
PID control to complete the implementation.
The following data values may be assigned to this parameter:
Parameter Value
Description
No PIDPID control is always inactive.
Dir F-FWDDirect action with feed-forward.
Rev F-FWDReverse action with feed-forward.
Dir F-FWD EDirect action with feed-forward, with PID enabled by DI.
Rev F-FWD EReverse action with feed-forward, with PID enabled by DI.
Dir FullDirect action with full range.
Rev FullReverse action with full range.
Dir Full EDirect action with full range, with PID enabled by DI.
Rev Full EReverse action with full range, with PID enabled by DI.
851 PID Feedback
Default: Vin1
Range: n/a
Level 2
The PID Feedback parameter configures the feedback signal to be used in PID control.
The following data values may be assigned to this parameter:
Parameter Value
Description
Vin1 Vin1 is the PID feedback.
Cin Cin is the PID feedback.
Vin2 Vin2 is the PID feedback.
EncoderThe Encoder is the PID feedback.
852 PID Prop Gain
Default: 0
Range: 0-2000
Level 2
The PID Proportional Gain parameter configures the proportional gain that is applied to the PID control.
Note: Value must be greater than 0 for this to be active.
853 PID Int Gain
Default: 0
Range: 0-10000
Level 2
The PID Integral Gain parameter configures the integral gain that is applied to the PID control.
Note: Value must be greater than 0 for this to be active.
854 PID Feed Gain
Default: 1000
Range: 0-2000
Level 2
The PID Feed Gain parameter allows the feedback signal to be scaled. A setting of 1000 indicates 100.0%.
855 PID Error 1
856 PID Error 2
Default: Read-Only
Range: 0.00-100.00%
Level 2
Both PID Error 1 and PID Error 2 parameters are read-only; they provide feedback on how the PID control
is operating.
857 PID High Corr
Default: 100.00%
Range: 0.00-100.00%
Level 2
This parameter sets the high limit of the PID output.
858 PID Low Corr
Default: 0.00%
Range: 0.00-100.00%
Level 2
This parameter sets the low limit of the PID output.
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......