vacon 500x parameters
7
613 Max Regen Ramp
Default: 300%
Range: 100 - 1001%
Level 2
This parameter operates as a percentage of the longest ramp time. This time then defines the amount of
time a deceleration to stop can take without causing a “Regen Timeout” fault. For example, if “Decel Time
1” is 5.0 seconds, “Decel Time 2” is 10.0 seconds, and “Max Regen Ramp” is 300%, a deceleration to stop
that takes more than 30 seconds will cause a “Regen Timeout” fault in the drive.
614 Stability Gain
Default: Model
dependent
Range: 0–10
Level 2
615 Stability Rate
Default: Model
dependent
Range: 1–1000
Level 2
Both of these parameters can be used to resolve stability problems if they occur. Use Parameter 615 if the
load has significant inertia with respect to the motor itself.
700 Vmet Config
Default: Freq Out
Range: n/a
Levels 1,2
This parameter configures the analog signal that will be applied to the Vmet output pin.
The following data values may be assigned to this parameter:
Para. Value
Description Range Limit
Freq OutOutput frequency of the driveParameter max freq.
Voltage OutVoltage being supplied to the motorRated motor voltage
Current OutCurrent being supplied to the motor200% of drive rating
Drive LoadCalculated percentage of drive rating200% of drive rating
Drive TempCalculation of total drive temp rating100% of unit temp rating
Stator FreqCommanded frequency100% of input config
Power OutCalculated power output of drive250% of drive rating
+/- LoadPercentage torque of drive-200 to +200% of drive rating
PID FbackAllows the analog output to produce
a signal in proportion to the PID
feedback received.
Vin 1Mirrors the status of the Vin1 input
0-100%
Cin Mirrors the status of the Cin input
0-100%
Vin 2Mirrors the status of the Vin2 input
0-100%
SIO ConfigAllows the serial port to set the Vmet
analog output through parameter 920
along with parameter 907 (Control Word)
EncoderMonitors the status of an encoder
connected to the drive through an option
board.
701 Vmet Span
Default: 100%
Range: 0.0%-200.0%
Level 2
This parameter sets the span of the Vmet analog output.
Summary of Contents for 500X
Page 1: ...vacon 500x ac drives user s manual ...
Page 13: ...24 hour support 358 0 40 837 1150 Email vacon vacon com introduction vacon z 12 1 ...
Page 117: ...24 hour support 358 0 40 837 1150 Email vacon vacon com troubleshooting vacon z 116 8 ...
Page 119: ...24 hour support 358 0 40 837 1150 Email vacon vacon com vacon 500x ultraflex options vacon 9 ...
Page 123: ......