118
•
vacon
parameter descriptions
9
2. When the Opening frequency limit has been reached the Open delay (P4.15)
must also elapse. Note! The output frequency is held at the Open frequency
limit until this.
3. When the two previous conditions are reached. The brake will open if the
output current is higher than the current limit.(P4.19)
Notice that any of the previous conditions can be left out by setting their val-
ues to zero.
Time
Output Frequency
Actual
Reference
P
Open Frequency Limit
P
Open delay
External Brake
1
2
1
= Open frequency Limit reached
2
3
= Open delay elapsed
= Brake opens if
External Brake:Current limit
is exceeded.
3
Brake
closed
Brake open
Relay
closed
Relay open
Figure 9.13: Starting / opening sequence with external brake
Closing brake conditions:
There are 2 conditions for closing the brake again. It’s enough that one is true
for the brake to close.
1. If there is no run command active and output frequency goes below Close
frequency limit (P4.17) or Close frequency limit in reverse (P4.18), depend-
ing on direction of rotation.
OR
2. Output current has gone below Current limit.(P4.19)
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...