parameters
vacon
•
93
8
8.17 Motor Pre-heat (Control panel: Menu PAR -> P16)
8.18 Easy usage menu (Control panel: Menu PAR -> P17)
Code
Parameter
Min
Max
Unit
Default
ID
Note
P16.1
0
2
0
1225
0 =
Not used
1 =
Always in stop state
2 =
Controlled by digital
input
P16.2
0
0,5 x
I
Nunit
A
0
1227
DC current for Pre-heat-
ing of motor and drive in
stop state. Active in stop
state or by digital input
while in stop state.
Table 8.17: Motor Pre-heat
Code
Parameter
Min
Max
Unit
Default
ID
Note
0
3
0
540
0 =
Basic
1 =
Pump
2 =
Fan drive
3 =
High Torque
NOTE!
Visible only when
Startup wizard is active.
P17.2
Parameter
conceal
0
1
1
115
0
= All parameters visible
1
= Only quick setup
parameter group visible
P17.3
Temperature
unit
0
1
0
1197
0
= Celsius
1
= Kelvins
NOTE!
Hidden until an
OPTBH board is con-
nected.
Table 8.18: Easy usage menu parameters
i
P17.1
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...