parameter descriptions
vacon
•
133
9
9.13 Automatic reset (Control panel: Menu PAR -> P14)
14.1 A
UTOMATIC
RESET
Activate the Automatic reset after fault with this parameter.
NOTE:
Automatic reset is allowed for certain faults only.
Fault:
1
. Under voltage
2
. Over voltage
3
. Over current
4
. Motor over temperature
5
. Under load
14.3 T
RIAL
TIME
The Automatic restart function restarts the frequency converter when the
faults have disappeared and the waiting time has elapsed.
The time count starts from the first auto reset. If the number of faults occur-
ring during the trial time exceeds trail number (the value of P14.4), the fault
state becomes active. Otherwise the fault is cleared after the trial time has
elapsed and the next fault starts the trial time count again. See Figure 9.22.
If a single fault remains during the trial time, a fault state is true.
Fault trigger
Motor stop signal
Motor start signal
Supervis ion
Restart 1
Restart 2
Trial time
par.14.3
Fault active
RESET/
Fault reset
Autoreset function: (Trials = 2)
Wait time
pa r.14.2
Wait t ime
pa r.14.2
Wait t ime
par.1 4.2
Figure 9.22: Example of Automatic restarts with two restarts
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...