parameter descriptions
vacon
•
135
9
15.11 S
LEEP
MIN
FREQUENCY
15.12 S
LEEP
DELAY
15.13 W
AKE
-
UP
ERROR
This function will put the drive into sleep mode if the frequency stays below the
sleep limit for a longer time than that set with the Sleep Delay (P15.12). This
means that the start command remains on, but the run request is turned off.
When the actual value goes below, or above, the wake-up error depending on
the set acting mode the drive will activate the run request again if the start
command is still on.
Wake up error
P15.13
Actual value
Frequency
Sleep min
frequency
P15.11
Regulating mode
Regulating mode
Sleep
P15.12
Sleep delay
Figure 9.24: Sleep min frequency, Sleep delay,Wake-up error
15.14 S
LEEP
SETPOINT
BOOST
15.15 S
ETPOINT
BOOST
TIME
15.16 S
LEEP
MAX
LOSS
15.17 S
LEEP
LOSS
CHECK
TIME
These parameters manage a more complex sleep sequence. After the time in
P15.12, the setpoint is increased of the term in P15.14, for the time in P15.15.
This will cause a higher output frequency.
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...