100
•
vacon
parameter descriptions
9
1 = Square:
The voltage of the motor changes following a squared curve form with
the frequency in the area from 0 Hz to the field weakening point where
the field weakening point voltage is also supplied to the motor. The
motor runs under magnetised below the field weakening point and
produces less torque, power losses and electromechanical noise.
Squared U / f ratio can be used in applications where torque demand
of the load is proportional to the square of the speed, e.g. in centrifugal
fans and pumps.
U[V]
f[Hz]
Un
Pa r. 1.11
Pa r. 1.14
Pa r. 1.10
Default: Nominal
voltage of the motor
Linear
Squared
Field weakening
point
Default: Nominal
frequency of the
motor
Figure 9.1: Linear and squared change of motor voltage
2 = Programmable U / f curve:
The U / f curve can be programmed with three different points. Pro-
grammable U / f curve can be used if the other settings do not satisfy
the needs of the application.
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...