fn
fn
t
t
t = 1 x par. 4.10
t = 0,1 x par. 4.10
0,1 x fn
RUN
STOP
RUN
STOP
Output frequency
Motor speed
Output frequency
Motor speed
DC-braking ON
DC-braking ON
fout
fout
116
•
vacon
parameter descriptions
9
Figure 9.10: DC-braking time when Stop mode = Coasting
Par. 2.3 = 1 (Stop function = Ramp):
After the Stop command, the speed of the motor is reduced according to the
set deceleration parameters, if the inertia of the motor and load allows that,
to the speed defined with parameter 4.11, where the DC-braking starts.
The braking time is defined with parameter 4.10. See Figure 9.11.
t = par. 4.
t
Par. 4.1
Motor speed
Output frequency
DC-braking
RUN
STOP
fout
1
10
Figure 9.11: DC-braking time when Stop mode = Ramp
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...