136
•
vacon
parameter descriptions
9
Frequency reference is then forced at minimum frequency and the feedback
value is sampled.
If the variation on the feedback value stays then lower than P15.16 for the time
in P15.17, the drive will enter sleep condition.
If this sequence is not needed, then program P15.14 = 0%, P15.15 = 0 s, P15.16
= 50%, P15.17 = 1 s.
15.18 P
ROCESS
UNIT
SOURCE
SELECTION
Monitor V4.5 can show a process value, proportional to a variable measured
by the drive. Source variables are:
0
= PID feedback value (max: 100%)
1
= Output frequency (max: fmax)
2
= Motor speed (max: nmax)
3
= Motor torque (max: Tnom)
4
= Motor power (max: Pnom)
5
= Motor current (max: Inom)
6
= Pulse train/ Encoder (max: 100%)
15.19 P
ROCESS
UNIT
DECIMAL
DIGITS
Number of decimals shown on monitor V4.5.
15.20
P
ROCESS
UNIT
MIN
VALUE
Value shown on V4.5 when source variable is at its minimum.Proportionality
is kept if source overtakes the minimum.
15.21 P
ROCESS
UNIT
MAX
VALUE
Value shown on V4.5 when source variable is at its maximum. Proportionality
is kept if source overtakes the maximum.
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...