fault tracing
5
52
Door Panel fault
Control place is keypad, but door
panel has been disconnected.
Check the connection
between optional board
and API. If connection is
correct, contact the near-
est Vacon distributor.
53
Fieldbus fault
The data connection between the
fieldbus Master and the fieldbus
of the drive has broken.
Check installation.
If installation is correct,
contact the nearest Vacon
distributor.
54
Slot fault
The connection between optional
board and API has been broken.
Check board and slot.
Contact the nearest Vacon
distributor.
55
Wrong run fault
Run forward and backward are
high at the same time.
Check I/O control signal 1
and I/O control signal 2.
57
Idenfication fault
Identification run has failed.
Run command was
removed before comple-
tion of identification run.
Motor is not connected to
frequency converter.
There is load on motor
shaft.
111
Temperature fault
Over low or over high temperature
Check temperature signal
from OPTBH board
Fault
code
Fault name
Possible cause
Correcting actions
Table 5.1: Fault codes
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...