parameters
vacon
•
91
8
P15.4
Feedback
source selection
0
Varies
1
334
0
= AI1
1
= AI2
2
= ProcessDataIn1
(0 -100%)
3
= ProcessDataIn2
(0 -100%)
4
= ProcessDataIn3
(0 -100%)
5
= ProcessDataIn4
(0 -100%)
6
= AI2-AI1
7
= Pulse train / encoder
8
= AIE1
9
= Temperature input 1
10
= Temperature input 2
11
= Temperature input 3
i
i
i
i
i
i
i
i
i
P15.5
0,0
50,0
%
0,0
336
Value at minimum signal
P15.6
10,0
300,0
%
100,0
337
Value at maximum signal
P15.7
0,0
1000,0
%
100,0
118
Proportional gain
P15.8
0,00
320,00
s
10,00
119
Integrative time
P15.9
0,00
10,00
s
0,00
132
Derivative time
P15.10
Error inversion
0
1
0
340
0
= Direct (Feedback < Set-
point ->Increase PID out-
put)
1
= Inverted (Feedback >
Setpoint ->Decrease PID
output)
P15.11
0,00
P3.2
Hz
25,00
1016
Drive goes to sleep mode
when the output frequency
stays below this limit for a
time greater than that
defined by parameter Sleep
delay
P15.12
0
3600
s
30
1017 Delay for enter sleep
P15.13
0,0
100,0
%
5,0
1018 Threshold for exit sleep
P15.14
0,0
50,0
%
10,0
1071 Referred to setpoint
Code
Parameter
Min
Max
Unit Default
ID
Note
Table 8.16: PID control parameters
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...