10.1 Vacon 20 technical data
Mains
connection
Input voltage U
in
115 V, -15%...+10% 1~
208…240 V, -15%...+10% 1~
208…240 V, -15%...+10% 3~
380 - 480 V, -15%...+10% 3~
600 V, -15%...+10% 3~
Input frequency
45…66 Hz
Line current THD
> 120%
Connection to mains
Once per minute or less (normal case)
Supply
network
Networks
Vacon 20 (400 V) cannot be used with corner grounded networks
Short circuit current
Maximum short circuit current has to be < 50 kA, For MI4 with-
out DC-choke, maximum short circuit current has to be < 2.3
kA, for MI5 without DC-choke, maximum short circuit current
has to be < 3.8 kA
Motor
connection
Output voltage
0 - U
in
Output current
Continuous rated current I
N
at ambient temperature max. +50
ºC (depends on the unit size), overload
1.5 x I
N
max
1 min / 10 min
Starting current /
torque
Current 2 x I
N
for 2 sec in every 20 sec period. Torque depends
on motor
Output frequency
0…320 Hz
Frequency resolution
0,01 Hz
Control
connection
Digital input
Positive, Logic1: 18…+30V, Logic0: 0…5V; Negative, Logic1:
0…10V, Logic0: 18…30V; Ri = 10K
Ω
(floating)
Analogue input volt-
age
0….+10V,Ri = 250K
Ω
Analogue input cur-
rent
0(4)…20mA, Ri
≤
250
Ω
Analogue output
0…10V, RL
≥
1K
Ω
; 0(4)…20mA,RL
≤
500
Ω
, Selectable through
microswitch
Digital output
Open collector, max. load 35V/50mA (floating)
Relay output
Switching load: 250Vac/3A
Auxiliary voltage
±20%,max.load 50mA
Table 10.1: Vacon 20 technical data
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...