parameter descriptions
9
9.2 Start / stop setup (Control panel: Menu PAR -> P2)
2.1
R
EMOTE
CONTROL
PLACE
SELECTION
With this parameter, the user can select the active control place, frequency
converter can be selected with P3.3/P3.12. The selections are:
0 =
I / O termina
1 =
Fieldbus
2 =
Keypad
Note:
You can select control place by pressing Loc / Rem button or with par.
2.5(Local / Remote), P2.1 will have no effect in local mode.
Local =
Keyp ad is the control place
Remote =
Control place determined by P2.1
2.2
S
TART
FUNCTION
The user can select two start functions for Vacon 20 with this parameter:
0 = Ramp start
The frequency converter starts from 0 Hz and accelerates to the set
frequency reference within the set acceleration time (See detailed de-
scription: ID103). (Load inertia, torque or starting friction may cause
prolonged acceleration times).
1 = Flying start
The frequency converter is able to start into a running motor by apply-
ing small current pulses to motor and searching for the frequency cor-
responding to the speed the motor is running at. Searching starts from
the maximum frequency towards the actual frequency until the cor-
rect value is detected. Thereafter, the output frequency will be in-
creased/decreased to the set reference value according to the set
acceleration/deceleration parameters.
Use this mode if the motor is coasting when the start command is giv-
en. With the flying start it is possible to start the motor from actual
speed without forcing the speed to zero before ramping to reference.
2.3 S
TOP
FUNCTION
Two stop functions can be selected in this application:
0 = Coasting
The motor coasts to a halt without control from the frequency convert-
er after the Stop command.
1 = Ramping
Summary of Contents for 20
Page 1: ...vacon 20 ac drives complete user manual ...
Page 2: ......
Page 6: ...1 ...
Page 12: ...6 vacon safety 1 ...
Page 27: ...installation vacon 21 3 ...
Page 28: ...22 vacon installation 3 MI1 MI5 3P 230 V POWER LOSS ...
Page 29: ...installation vacon 23 3 ...
Page 30: ...24 vacon installation 3 ...
Page 31: ...installation vacon 25 3 MI1 MI3 1P 230 V POWER LOSS ...
Page 32: ...26 vacon installation 3 ...
Page 40: ...34 vacon installation 3 Figure 3 23 Open the lid MI1 MI3 Figure 3 24 Open the lid MI4 MI5 ...
Page 43: ...installation vacon 37 3 4 5 6 ...
Page 52: ...46 vacon installation 3 ...
Page 76: ...70 vacon control panel 7 ...
Page 104: ...98 vacon parameters 8 ...
Page 152: ...146 vacon parameter descriptions 9 ...
Page 158: ...152 vacon technical data 10 ...
Page 159: ......
Page 160: ...Rev E2 Document ID ...