6
vacon • 69
Commissioning
6.4
Maintenance
In normal conditions, the AC drive is maintenance-free. However, regular maintenance is rec-
ommended to ensure trouble-free operation and longevity of the drive. We recommend the ta-
ble below is followed for maintenance intervals.
Maintenance interval
Maintenance action
Regularly and according to
general maintenance interval
•
Check tightening torques of terminals
6...24 months (depending on
environment)
•
Check input and output terminals and
control I/O terminals.
•
Check for corrosion on terminals and
other surfaces
•
Check door filter in case of cabinet
installation
24 months
•
Clean heatsink
12...24 months
•
Charge capacitors, only after long
storage times or long down times
without supply: contact your nearest
Vacon service center