5
vacon • 57
Control unit
5.1.7
Selection of terminal functions with dip switches
VACON
®
20 Cold Plate drive embodies four so-called
switches
that allow for two functional se-
lections each. The shadowed terminals in Table 24 can be functionally modified with the dip
switches.
The switches have two positions: 0 and 1. See Figure 32 to locate the switches and make ap-
propriate selections for your requirements.
Figure 32. Dip switches
5.1.7.1
Switch SW1
The digital inputs (terminals 8-10 and 14-16) on the standard I/O board can be
isolated
from
ground by setting the
dip switch SW1
to position ‘1’. See Figure 32. Locate the switch and set
it in the desired position. The switch in the position “0” means that the common of digital input
have been connected to the ground.The default position is “0”.
5.1.7.2
Switches SW2 and SW3
Analogue inputs can be used as either current inputs or voltage inputs. The signal type is se-
lected with two switches on the control board.
The switch SW2 is related to analogue input AI1. In position “1” the analogue input AI1 works
in voltage mode. In position “0” the analogue input works in current mode. The default position
for SW2 is “1”.
The voltage range is 0...10V and the current is 0/4.....20 mA.
The switch SW3 is related to analogue input AI2. In the position “1” the analogue input AI2
works in voltage mode. In the position “0” the analogue input works in current mode. The de-
fault position for SW3 is “0”.
The voltage range is 0...10V and the current is 0/4.....20 mA.
5.1.7.3
Switch SW4
The switch SW4 is related to the RS485 connection. It’s used for bus termination. The bus ter-
mination must be set to the first and to the last device on the network. The switch SW4 in po-
sition “0” means that termination resistance is connected and the termination of the bus has
been set. If the Vacon 20 CP is the last device on the net, this switch must be set to “0” position.
The default position for SW4 is “0”.
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...