Power cabling
4.7
Cable installation
•
Before starting, check that none of the components of the AC drive is live. Read the
warnings in chapter 1 carefully
•
Place the motor cables sufficiently far from other cables
•
Avoid placing the motor cables in long parallel lines with other cables.
•
If the motor cables run in parallel with other cables note the minimum distances
between the motor cables and other cables given in table below.
•
The given distances also apply between the motor cables and signal cables of other sys-
tems.
•
The
maximum length
for motor cables is
30m
•
The motor cables should cross other cables at an angle of 90 degrees.
•
If cable insulation checks are needed, see chapter Cable and motor insulation checks.
Start the cable installation according to the instructions below:
Figure 22. Stripping of cables.
Table 19. Cables stripping lengths [mm].
Distance between cables, [m]
Shielded cable, [m]
0.3
≤
50
1.0
≤
200
1
Strip the motor and mains cables as recommended below.
Frame
A1
B1
C1
D1
C2
D2
E
MS2
8
8
8
20
36
20
Leave as short
as possible
MS2
1-phase
7
8
8
20
36
20
MS3
8
8
8
20
36
20
D1
B1
C1
A1
D2
C2
E
Earth conductor
MAINS
MOTOR
Shield
Earth conductor
D1
B1
C1
A1
Earth conductor
MAINS
(1-phase)
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...