Safe Torque Off
9.3
Standards
The STO function has been designed for use in accordance with the following standards:
The STO function has to be applied correctly to achieve the desired level of operational safety. Four
different levels are allowed, depending on the use of the STO signals (see the following table).
The same values are calculated for SIL and SIL CL. According to EN 60204-1, the emergency stop
category is 0.
The SIL value for the safety related system, operating in high demand/continuous mode, is related
to the probability of dangerous failure per hour (PFH), reported in the following table.
Standards
IEC 61508, Parts 1-7
EN 61800-5-2
EN 62061
ISO 13849-1
EN 954-1
IEC 60204-1
Table 41. Safety Standards.
STO inputs
STO feedback
Cat.
PL
SIL
Both dynamically used(*)
Used
4
e
3
Both statically used
Used
3
e
3
Connected in parallel
Used
2
d
2
Connected in parallel
Not used
1
c
1
Table 42. Four different STO levels. (*) see 9.5.1.
STO inputs
STO feedback
PFH
PFDav
MTTFd
(years)
DCavg
Both dynamically used(*)
Used
8.0 E-10 1/h
7.0 E-05
8314 y
HIGH
Both statically used
Used
8.1 E-10 1/h
7.1 E-05
8314 y
MEDIUM
Connected in parallel
Used
8.1 E-10 1/h
7.1 E-05
8314 y
MEDIUM
Connected in parallel
Not used
9.2 E-10 1/h
8.0 E-05
8314 y
NONE
Table 43. SIL values. (*) see 9.5.1.
The STO inputs must always be supplied by a safety device.
The power supply of the safety device may be external or taken from the drive (as
long as this is compliant with the rating specified for terminal 6).
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...