vacon • 71
Technical data
7.1.3
Mains voltage 3AC 380-480V
NOTE:
The rated currents in given ambient temperatures (in Table 32) are achieved only when
the switching frequency is equal to or less than the factory default.
7.1.4
Definitions of overloadability
Overloadability
=Following continuous operation at rated output current I
N
, the converter supplies
150% * I
N
for 1 min, followed by a period of at least 9 min at I
N
or below.
Example:
If the duty cycle requires 150% rated current for 1 min in every 10 min, the remaining 9
min must be at rated current I
N
or less.
Figure 39. High overload.
Mains Voltage 3AC 380-480V, 50/60 Hz
Converter
type
Input
current
[A]
Loadability
Motor shaft power
400V
480V
Rated continuous
current IN
[A]
50% overload
current
[A]
Max current
IS
[kW]
[HP]
MS2
0003
3.2
2.4
3.6
4.8
0.75
1.0
0004
4.0
3.3
5.0
6.6
1.1
1.5
0005
5.6
4.3
6.5
8.6
1.5
2.0
0006
7.3
5.6
8.4
11.2
2.2
3.0
0008
9.6
7.6
11.4
15.2
3.0
4.0
MS
3
0009
11.5
9.0
13.5
18.0
4.0
5.0
0012
14.9
12.0
18.0
24.0
5.5
7.5
0016
20
16.0
24.0
32.0
7.5
10.0
Table 32. Power ratings of
VACON
®
20 CP, supply voltage 3AC 380-480V.
I
N
IN*150%
1 min
9 min
IN*150%
Current
Time
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...