Power cabling
vacon • 44
Service support: find your nearest Vacon service center at www.vacon.com
4
Tightening torques of cable terminals:
Table 20. Tightening torques of terminals.
2
Connect the stripped cables:
•
Expose the shield of both cables in order to make a 360-degree connection
with the cable clamp.
•
Connect the phase conductors of the supply and motor cables into their
respective terminals.
•
Form the rest of the cable shield of both cables into “pigtails” and make a
grounding connection with the clamp. Make the pigtails just long enough
to reach and be fixed to the terminal - no longer.
Frame
Type
Tightening torque
Power and motor
terminals
Tightening torque
EMC grounding
clamps
Tightening torque,
Grounding terminals
[Nm]
lbs-in.
[Nm]
lbs-in.
[Nm]
lbs-in.
MS2
0003 4—0008 4
0004 2—0007 2
0.5—0.6
4.5—5.3
1.5
13.3
2.0
17.7
MS3
0009 4—0016 4
0011 2—0017 2
1.2—1.5 10.6—13.3 1.5
13.3
2.0
17.7