Safe Torque Off
vacon • 104
Service support: find your nearest Vacon service center at www.vacon.com
9
9.5.4
Safety Capability Cat. 1 / PL
c
/ SIL 1
Without any automatic monitoring of STO output feedback, the safety capability is reduced to Cat. 1
/ PL c / SIL 1. The STO inputs (which can be connected in parallel) must be supplied by a safety push
button or a safety relay.
The picture below shows an example of connection for the STO function. A switch (a safety push but-
ton or a safety relay) may be connected with 2 wires to the drive.
When the contacts of the switch are opened, the STO is demanded, the drive indicates F30 (= "Safe
Torque Off") and the motor stops by coasting.
Figure 56. STO example without automatic monitoring of the feedback and STO inputs connect-
ed in parallel. (*)Only for MS3.
The choice of using the STO inputs (without the automatic monitoring of the output
feedback) does not allow the
other safety capabilities to be achieved
.
The standards for functional safety require that functional proof tests are performed
on the equipment at user-defined intervals. Therefore,
this safety capability
can be
achieved, as long as the STO function is manually monitored at the proof test interval
determined by the specific application (once a month can be acceptable).
This
safety capability
can be achieved by connecting in parallel the STO inputs exter-
nally and by ignoring the use of the STO output feedback.
R
R
R
R
=
3
S1
G1
S2
G2
L1
L2
L3
F+
F-
U
V
W
DC+/R+
R-
DC-*
SWITCH
Reinforced
POWER UNIT
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...