Safe Torque Off
vacon • 102
Service support: find your nearest Vacon service center at www.vacon.com
9
The picture below shows an example of connection for the STO function. The external device has to
be connected with 6 wires to the drive.
Figure 54. STO example with automatic monitoring of the feedback and both STO inputs used.
(*) Only for MS3.
The external device has to monitor the STO function in accordance with theTable 44. The device has
to periodically de-energize the STO inputs and it has to verify that the STO output feedback assumes
the expected value.
Any difference between the expected and the real value has to be considered as a failure and has to
drive the system into a Safe State. In case of failure, check the wiring. If the fault recognized by the
external safety device persists,
the drive will have to be replaced/repaired
.
R
R
R
R
=
3
S1
G1
S2
G2
L1
L2
L3
F+
F-
U
V
W
DC+/R+
R-
DC-*
Reinforced
POWER UNIT
EXTERNAL DEVICE