Power cabling
Use cables with heat resistance in accordance with the application requirements. The cables
and the fuses must be dimensioned according to the AC drive nominal OUTPUT current which
you can find on the rating plate.
1 = Power cable intended for fixed installation and the specific mains voltage. Shielded
cable not required. (MCMK or similar recommended).
2 = Symmetrical power cable equipped with concentric protection wire and intended for the
specific mains voltage. (MCMK or similar recommended). See Figure 18.
3 = Symmetrical power cable equipped with compact low-impedance shield and intended
for the specific mains voltage. [MCCMK, EMCMK or similar recommended; Recom-
mended cable transfer impedance (1...30MHz) max. 100mohm/m]. See Figure 18.
*360º earthing of the shield with cable glands in motor end needed for EMC category C1
and C2.
4 = Screened cable equipped with compact low-impedance shield (JAMAK, SAB/ÖZCuY-O
or similar).
Figure 18. Example with three-phase cable.
NOTE
: The EMC requirements are fulfilled at factory defaults of switching frequencies (all
frames).
NOTE:
If safety switch is connected the EMC protection shall be continuous over the whole ca-
ble installation.
EMC levels
Cable type
1
st
environment
2
nd
environment
Category C1 and C2
Category C3
Category C4
Mains cable
1
1
1
Motor cable
3*
2
2
Control cable
4
4
4
Table 13: Cable types required to meet standards.
Shield
PE conductors
Shield
PE conductor
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...