Safe Torque Off
vacon • 106
Service support: find your nearest Vacon service center at www.vacon.com
9
9.7
Parameters and fault tracing
There are no parameters for the STO function itself.
To re-enable motor operation, after the STO state, it is necessary to perform the following steps:
•
Release the switch or the external device (“F30” is displayed even after this has been
released).
•
Reset the fault (through a digital input or from the keypad).
•
It is possible that a new start command is required for the restart (depending on the applica-
tion and your parameter settings).
Before testing the STO function, make sure that the checklist (Table 48) is inspected
and completed.
When STO function is demanded, the drive always generates a fault (“F30”) and the
motor stops by coasting.
In the application the STO state can be indicated using a digital output.
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...