3
vacon • 29
Mounting
3.6
Power loss thermal characteristics
In the table below are the thermal characteristics of VACON
®
20 CP AC drive at nominal output
current. The power loss in stand-by conditions is 12 W for all sizes (supply voltage 24 V, 100
mA).
Mains voltage 3AC 208-240V, 50/60 Hz
Frame
Converter
Type
Rated output
current [A]
Cold plate
loss [W]
Internal loss
[W]
Total loss
[W]
MS2
0004
3.7
27
18
45
0005
4.8
37
21
58
0007
7.0
58
30
88
MS3
0011
11.0
85
28
113
0012
12.5
101
37
138
0017
17.5
146
50
196
Table 8. Drive power loss at rated conditions, voltage range 3AC 208-240V.
Mains voltage 1AC 208-240V, 50/60 Hz
Frame
Converter
Type
Rated output
current [A]
Cold plate
loss [W]
Internal loss
[W]
Total loss
[W]
MS2
0004
3.7
31
22
53
0005
4.8
37
24
61
0007
7.0
59
31
90
Table 9. Drive power loss at rated conditions, voltage range 1AC 208-240V.
Mains voltage 3AC 380-480V, 50/60 Hz
Frame
Converter
Type
Rated output
current [A]
Cold plate
loss [W]
Internal loss
[W]
Total loss
[W]
MS2
0003
2.4
23
16
39
0004
3.3
31
18
49
0005
4.3
43
21
64
0006
5.6
58
25
83
0008
7.6
84
33
117
MS3
0009
9.0
86
31
117
0012
12.0
120
37
157
0016
16.0
171
48
219
Table 10. Drive power loss at rated conditions, voltage range 3AC 380-480V.
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...