Control unit
vacon • 50
Service support: find your nearest Vacon service center at www.vacon.com
5
5.1.2
Standard I/O terminals
The terminals of the
Standard I/O
are described below. For more information on connections,
see chapter 7.3.1.
The terminals shown on shadowed background are assigned for signals with optional functions
selectable with DIP switches. For more information, see chapter 5.1.7.
Table 24. Control I/O terminal signals and connection example.
Standard I/O terminals
Terminal
Signal
A
RS485_A
Serial bus, negative
B
RS485_B
Serial bus, positive
1
+10 Vref
Reference output
2
AI1+
Analogue input,
voltage or current
3
GND
I/O signal ground
6
24Vout
24V aux. voltage
7
DIN COM
Digital inputs com-
mon
8
DI1
Digital input 1
9
DI2
Digital input 2
10
DI3
Digital input 3
4
AI2+
Analogue input,
voltage or current
5
GND
I/O signal ground
13
DO1-
Digital output 1 com-
mon
14
DI4
Digital input 4
15
DI5
Digital input 5
16
DI6
Digital input 6
18
AO1+
Analogue signal
(+output)
20
DO1+
Digital output 1
V
X1
Remote reference
4...20mA/0...10V
Reference potentiometer
1...10k
Ω
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...