Control unit
vacon • 60
Service support: find your nearest Vacon service center at www.vacon.com
5
5.2.2
Preparation for use through RS485
1
Strip about 15 mm of the RS485 cable (see specification on Table 29) and cut off
the grey cable shield. Remember to do this for both bus cables (except for the
last device).
Leave no more than 10 mm of the cable outside the terminal block and strip the
cables at about 5 mm to fit in the terminals. See picture below.
Also strip the cable now at such a distance from the terminal that you can fix it to
the frame with the grounding clamp. Strip the cable at a maximum length of 15
mm.
Do not strip the aluminium cable shield!
2
Then connect the cable to its appropriate terminals on VACON
®
20 CP AC drive
standard terminal block, terminals
A and B
(A = negative, B = positive).
3
Using the cable clamp included in the supply of the drive, ground the shield of
the RS485 cable to the frame of the AC drive.
4
If VACON
®
20 Cold Plate drive is the last device on
the bus
, the bus termination must be set. Locate the
switches to the right of the control terminals (see
Figure 32) and turn the SW4 switch to position “0”.
Biasing is built in the termination resistor.
5
NOTE:
When planning the cable runs, remember to keep the distance between
the fieldbus cable and the motor cable at a
minimum of 30 cm
.
6
The bus termination must be set for the first and the last device of the fieldbus
line. We recommend that the first device terminated is the Master device.
10
5
Summary of Contents for 20 CP
Page 1: ...vacon 20 cp ac drives installation Technical and Maintenance manual ...
Page 2: ......
Page 6: ...vacon 3 ...
Page 16: ...1 vacon 13 Safety Figure 6 STO certificate ...
Page 18: ...1 vacon 15 Safety ...
Page 24: ...vacon 21 Receipt of delivery 2 ...
Page 36: ...3 vacon 33 Mounting ...
Page 48: ...4 vacon 45 Power cabling ...
Page 64: ...5 vacon 61 Control unit ...