Configuration and Operation
Sageon III Power System
PM990-8800-00, Rev. 9
4-26
(Battery Menu continued)
More detailed explanations of all the menu items are available in the Controller Operation PDF on the Manual CD
ENTER
Enable/disable Equalisation charging
Equalisation
On
ENTER toggles state
Off / On
ENTER
Charge current limit for battery voltage
BILim Vb>Vfl
20A
Modify Value up/down
ENTER to accept
between float & equalise
ENTER
System Equalise voltage without BTC.
System Equalise
56.5V
Modify Value up/down
ENTER to accept
Sense point voltage regulated to this value
ENTER
Enable/disable bus voltage discharge
Volts Start Eq
On
ENTER toggles state
Off / On
triggering of equalisation charging
ENTER
Threshold below which Eq is triggered
Volts Eq Trigger
46.0V
Modify Value up/down
ENTER to accept
ENTER
Enable/disable battery capacity loss
Q Start Eq
On
ENTER toggles state
Off / On
triggering of equalisation charging
ENTER
Threshold below which Eq is triggered
Q Loss Trigger
25Ah
Modify Value up/down
ENTER to accept
ENTER
Battery charging current below which
EQ End Current
15A
Modify Value up/down
ENTER to accept
equalisation charging terminates
ENTER
Maximum duration of equalisation
EQ Duration
3 hours
Modify Value up/down
ENTER to accept
ENTER
Periodic equalisation charging trigger
EQ Period
12 Weeks
Modify Value up/down
ENTER to accept
Set to zero to disable
ENTER
Manual control of equalisation
Manual Start Eq
Press ENTER
ENTER toggles state
Start / Stop
ENTER
Battery voltage below which the LVDS
LVDS Trip
43.0V
Modify Value up/down
ENTER to accept
opens when in Auto mode.
ENTER
LVDS (where used) operation mode.
(
↑
)
LVDS Mode
Auto
Modify Value up/down
ENTER to accept
[Auto, Open, or Closed]
DEC
ENTER
Enable/disable battery overtemperature
Temp Sen Alarm
On
ENTER toggles state
Off / On
alarm - set to off if no sensor used.
INC
ENTER
Periodic battery discharge test trigger
(
↓
)
BDT Period
14 Days
Modify Value up/down
ENTER to accept
Set to zero to disable
ENTER
Time of day to begin automatic
BDT Time
21:35
Modify Value up/down
ENTER to accept
discharge testing
ENTER
Maximum duration of a discharge test
BDT Duration
1h30min
Modify Value up/down
ENTER to accept
ENTER
Discharge test current (controlled)
BDT Current
50A
Modify Value up/down
ENTER to accept
Load must be > the value programmed
ENTER
Battery voltage below which the BDT
BDT End V
46.5V
Modify Value up/down
ENTER to accept
terminates.
ENTER
Battery loss of capacity below which
BDT End Q
150Ah
Modify Value up/down
ENTER to accept
the BDT terminates.
Result of the Last discharge test
Last BDT
Passed