Sageon III Power System
Commissioning
PM990-8800-00, Rev. 9
3-11
TCP/IP and Sageview Interface
The interface is a 10/100BASE-T Ethernet adaptor. The TCP/IP port sends Controller data over a network to a PC running Sageview
control and monitoring software. The Sageview interface provides this function for up to 2 PCs on the network simultaneously as well
as providing SNMP traps on alarms, system time synchronization to a global clock if access to the internet is available, and a
simplified system status Webpage (HTTP). If direct connection to a PC network port is required, a cross-over network cable should
be used. To set up Sageview, follow the instructions on the installation CD.
To enable network access on the TCP/IP port, an IP address must be assigned to the port. If access over the Internet is considered, the
gateway address must be programmed as well. There are several methods to do that, two are recommended and are described in
section 7.1. Other operating parameters of the interface are pre-programmed and should not be changed. Factory default IP address is
192.168.10.60.
To be able to assign a network address, the Ethernet address (referred to also as hardware address or MAC ID) of the interface must be
known. On the Power plant top cover is a small label indicating the MAC ID similar to one shown below.
Note: The interface IP address cannot be changed until the Power plant has been commissioned and the Controller is operational.
3.10 BATTERY DISTRIBUTION MODULE
The battery distribution module is capable of handling up to four battery strings.
Connect the current transducer signal cable to the appropriately labeled connector on the circuit board.
AU
X
S
W
AU
X
S
W
N
O
.
4
AU
X
S
W
N
O
.
3
AU
X
S
W
N
O
.
2
AU
X
S
W
N
O
.
1
C
O
M
FIGURE 3-9 BATTERY DISTRIBUTION MODULE (BDM)
The MAC ID can have
format 00-20-4A-24-BB-42
or 00:20:4A:24:BB:52.