Sageon III Power System
Configuration and Operation
PM990-8800-00, Rev. 9
4-23
(Base Menu continued)
ENTER
3-ph AC Monitor
Off
INC/DEC toggles state
ENTER to accept
(If 3-ph AC Monitor not = Off)
ENTER
3ph AC Vhi Alarm
260V
Modify Value up/down
ENTER to accept
ENTER
3ph AC Vlo Alarm
200V
Modify Value up/down
ENTER to accept
ENTER
3ph AC fhi Alarm
55.0Hz
Modify Value up/down
ENTER to accept
ENTER
3ph AC flo Alarm
45.0Hz
Modify Value up/down
ENTER to accept
ENTER
3ph AC FS Curr.
100A
Modify Value up/down
ENTER to accept
ENTER
Battery Monitor
Off
INC/DEC toggles state
ENTER to accept
(If Battery Monitor not = Off)
ENTER
Selects battery cell type
Battery Config
24 cells
Modify Value up/down
ENTER to accept
ENTER
Number of battery banks
BCM Batteries
1
Modify Value up/down
ENTER to accept
ENTER
Cell Vhi Alarm
2.50V
Modify Value up/down
ENTER to accept
ENTER
Cell Vlo Alarm
1.80V
Modify Value up/down
ENTER to accept
ENTER
Differential cell threshold
Cell +dVc Alarm
10%
Modify Value up/down
ENTER to accept
ENTER
Differential cell threshold
Cell -dVc Alarm
10%
Modify Value up/down
ENTER to accept
ENTER
Site Monitor
Off
INC/DEC toggles state
ENTER to accept
(If Site Monitor not = Off)
ENTER
Status of output relay 1
Output 1
Off
Modify Value up/down
ENTER to accept
ENTER
Status of output relay 2
Output 2
Off
Modify Value up/down
ENTER to accept
ENTER
Status of output relay 3
Output 3
Off
Modify Value up/down
ENTER to accept
ENTER
Status of output relay 4
Output 4
Off
Modify Value up/down
ENTER to accept