Configuration and Operation
Sageon III Power System
PM990-8800-00, Rev. 9
4-8
Access the screen series shown here by pressing the “up arrow” button. Press the “down arrow” button to access the screens in reverse
order.
Home screen
“C” indicates that the battery temperature compensation is active
Ambient temperature is displayed in degrees Centigrade
Ambient temperature alarm level
3-Phase AC monitor voltage, current, and frequency
Use “up arrow” or “down arrow” to scroll through the three AC inputs for each
parameter. AC monitor option must be installed to view these screens.
Programmable parameters:
This series of screens contain programmable parameters. To change a parameter value:
1.
Scroll to the desired screen using the “up arrow” or “down arrow” button.
2.
Press the ENTER button; the selected value will flash.
3.
Use the “up arrow” or “down arrow” button to edit that value. Press ENTER to store the new value or to move to the next number
to be set in a series of numbers.
Float voltage high level: Set to the desired high alarm value.
Float voltage low level: Set to the desired low alarm value.
Failsafe Alarms: When Failsafe alarms are on, all alarm relays will be normally energized
when no alarm condition is present. Relays will de-energize when an alarm occurs.
Battery current sensor: When Battery current sensor is turned on, the controller will read
battery current from the installed battery current transducers.
Security on/off toggle: When security is On, no parameter values may be edited. Without
first entering the password; this menu will not appear if a password has not been set.
Password Setup: The Sageon systems are shipped without a password set by default.
Enter a password to prevent unauthorized changes to system parameters.
Controller features password security for setting of parameter. A valid password is an
alphanumerical code having minimum three and maximum eight characters.
155A 54.2V
FL
155A 54.2V
FLC
Ambient Temp
31°C
Ambient Temp Alarm
45°C
Volts High Alarm
57.5V
Volts Low Alarm
48.0V
Security
On
Password Setup
Press ENTER
3-Ph AC1 Volts
216V
Bat Cur Sensor
On
Failsafe Alarms
On
Wrong Password
Panel Locked