Configuration and Operation
Sageon III Power System
PM990-8800-00, Rev. 9
4-6
Alarm Name
Comment
LED ON/FL
battery cell voltage
Range SMR
SMR parameter range error. SCU could not overwrite values
Amber (FL)
Site Monitor
Alarm preset from the site monitor System. See site monitor menu for details of alarm
channel
Amber (FL)
Battery Disch
Batteries are discharging
Amber (FL)
Disch Tst Fail
Battery discharge test failed to reach a programmed end point
Amber (FL)
SMR Comms Fail
One or more SMRs are not responding
Amber (FL)
Amb Temp High
Ambient temperature higher than preset limit
Amber (FL)
Batt Temp High
Battery temperature higher than preset limit
Amber (FL)
Batt Temp Sens
Battery temperature sensor not connector or failure
Amber (FL)
Batt I-Limit
Battery charging current is being limited to preset value
Amber (FL)
Bat Sym Alarm
Battery discharge currents from battery strings not sharing load equally
Amber (FL)
Equalize
System is in equalize mode
Amber (On)
Table Notes: FL = LED Flashing; On = LED On Steady