Configuration and Operation
Sageon III Power System
PM990-8800-00, Rev. 9
4-12
SMR no response: A No Response message appears when the target Rectifier is not
installed, not connected, not switched On, or is faulty.
SMR initial display: When a Rectifier is online and operating normally, its output current
and heatsink temperature are shown.
SMR version and temperature: Press enter display Rectifier’s software version.
SMR output current: Press the “up arrow” button to display the output current from other
Rectifiers.
Float voltage: This parameter is globally (and indirectly) set in the Batt menu. It cannot
be changed in this screen.
Equalization voltage: This parameter is globally (and indirectly) set in the Batt menu. It
cannot be changed in this screen.
Programmable Parameters:
The following screens allow access to the SMR programmable parameters.
Note that the parameter values apply to ALL installed SMRs. To change a parameter
value:
1.
Scroll to the desired screen using the “up arrow” or “down arrow” button.
2.
Press the ENTER button; the selected value will flash.
3.
Use the “up arrow” or “down arrow” button to edit that value. Press ENTER to store the new value.
SMR high voltage alarm threshold:
SMR low voltage alarm threshold:
SMR high voltage (DC) shutdown:
SMR current limit:
Fault reset: Press ENTER to reset latched alarms, such as HVSD. The Rectifier will
restart unless damaged or faulty.
Note: Pressing “up arrow” button will display the HOME screen.
SMR1
No Response
SMR1
92A 29°C
SMR1
G1045a
SMR2
91A
SMR Float
54.2V
SMR Equalize
57.0V
SMR V high Alarm
57.0V
SMR V low Alarm
48.0V
SMR HVSD
58.0V
SMR I Limit
50A
Reset SMR Fault
Press ENTER