Sageon III Power System
Configuration and Operation
PM990-8800-00, Rev. 9
4-25
Battery Menu (Battery Specific Functions)
Home Screen
25.2A 54.3V
FL
⇒
BATT Button
Battery string 1 current
Battery 1
12A Discharging
Additional screens if more batteries declared
(
↑
)
:
:
DEC
Battery 4
10A Discharging
INC
Shows "Not Available" if no sensor connected or "Sensor Fail" is faulty
(
↓
)
Battery Temp
35°C
Estimated remaining charge
Estimated Q Bat1
300Ah
Additional screens if more batteries declared
:
:
Estimated Q Bat4
300Ah
ENTER
Bus voltage below which alarm flagged
Batt Disch Alarm
47.0V
Modify Value up/down
ENTER to accept
ENTER
Alarm threshold for poor battery
Disch I Diff
20A
Modify Value up/down
ENTER to accept
current sharing, shows if >1 battery
ENTER
Battery temperature above which alarm
Batt Temp Alarm
50°C
Modify Value up/down
ENTER to accept
flagged. Not active without sensor.
ENTER
Battery capacity (C10) in Ah
Battery Rating
500Ah
Modify Value up/down
ENTER to accept
ENTER
Battery Temperature compensation.
BTC Coeff.
3.2 mV/C/°C
Modify Value up/down
ENTER to accept
Variable from 0 to 6.0mV/C/°C
(If BTC not = Off)
ENTER
Mid point temp for BTC curve (Comp.=0)
BTC Nominal
20°C
Modify Value up/down
ENTER to accept
ENTER
Number of Cells
24
Modify Value up/down
ENTER to accept
Physical number of 2V cells in string - used for BTC
ENTER
Charge current limit for recovery of
(
↑
)
BILim Vb<Vdd
32A
Modify Value up/down
ENTER to accept
deep discharged batteries
DEC
ENTER
Battery voltage below which the battery
Vdd Level
43.5V
Modify Value up/down
ENTER to accept
is considered to be deep discharged
INC
ENTER
Charge current limit for battery voltage
(
↓
)
BILim Vb<Vfl
40A
Modify Value up/down
ENTER to accept
between deep discharge & float
ENTER
System Float voltage without BTC.
System Float
54.0V
Modify Value up/down
ENTER to accept
Sense point voltage regulated to this value
ENTER
Estimated max. resistive drop between the
System V Drop
0.8V
Modify Value up/down
ENTER to accept
SMRs and the system voltage sense point.