Sageon III Power System
Configuration and Operation
PM990-8800-00, Rev. 9
4-11
The following screens
will not appear
if Off has been entered.
Battery configuration: Set the number of cells in a battery string and the number of
battery strings connected to the monitor. See Section 4.9 Sageon III Battery Monitor
Setup for details.
After pressing ENTER, “current configuration” will flash. Scroll through the available
configurations and press ENTER again once the correct battery type is chosen.
Battery strings: Set the number of connected battery strings. The maximum is four.
Note: This number must equal to or be less that the Num of Batteries entered in the Home, Programmable Parameters series of
screens.
High voltage alarm threshold: Set the cell voltage above which an alarm will be
generated.
Low voltage alarm threshold: Set the cell voltage below which an alarm will be
generated.
Delta positive voltage threshold: Set the percentage of nominal cell voltage by which any
individual cell voltage can exceed the nominal. Above this value, an alarm will be
generated.
Delta negative voltage threshold: Set the percentage of nominal cell voltage by which any
individual cell voltage can be less than the nominal. Below this value, an alarm will be
generated.
Site Monitor
When the Site Monitor is included in the software, the window at right will appear next.
Site monitor on/off toggle: Press ENTER to display the current On/Off status (flashing).
Press “up arrow” or “down arrow” to set the desired state, then press ENTER to store.
Contact the factory for additional details concerning this feature.
4.6 RECT (RECTIFIER) MENU SCREENS
Enter this series of menus by pressing the REC (SMR) button. Press “up arrow” or “down arrow” to select the Rectifier number (i.e.
rectifier position address) and press ENTER. Press “up arrow” to scroll through the screens in the order shown. Repeat for each
Rectifier. The following map summarizes the available menu screens.
RECT Button
Select Rectifier number* (1-24); read
number, current, and temperature
Press ENTER for firmware version
Float voltage
Equalization voltage
Programmable
Voltage, high/low alarm
Voltage, high voltage shutdown
Current limit
Fault, reset SMR
*
The Rectifier number is the “rectifier position address” of the target Rectifier (e.g. SMR
“4”
).
Bat Config
24 cells
SBM Batteries
2
Cell Vhi Alm
2.48V
Cell Vlo Alm
1.44V
Cell +dVc Al
10%
Cell -dVc Al
10%
Site Monitor
Press ENTER
Site Monitor
On