ACE-tronics G9 ASD Installation and Operation Manual
89
Automatic Function Selection
Program
Utilities
Display Parameters
This parameter setting is used to configure multiple parameters with the setting
of only one parameter. From the selection below multiple parameters may be
set as indicated in the table.
Once set, the selected configuration is placed in effect and remains in effect
until this parameter is changed or the individual settings are changed.
Set this parameter to Disable to set these parameters individually.
Note:
After performing the desired selection the EOI display returns to
Disabled though the selected function has been carried out (i.e.,
without this, if selection 1 is performed,
F004
and
F207
would
hold the RR terminal setting regardless of attempts to change the
settings individually).
Settings:
Disabled
RR
V/I
RR or V/I Switched via Terminal Board (ACE G9-120V-PCB)
Keypad Frequency/Terminal Board Command (ACE G9-120V-PCB)
Keypad Frequency and Command
Direct Access Number — F040
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
User Settings
Related
Params
Default
Settings
0
-Disable
1
-RR
2
-V/I
3
-RR or
V/I via TB
4
-Keypad/
Freq.
CMD/TB
5
-Keypad
Freq/CMD
Command
Mode
F003
Terminal
Board
N/C
Terminal
Board
*Keypad
Frequency
Mode 1
F004
RR
N/C
RR
N/C
RR
*Keypad
I3 Terminal
F117
Preset
Speed 3
N/C
Freq.
Ref.
Priority
N/C
Freq.
Priority
F200
Terminal
Board
N/C
Terminal Board
V/I
Setup
F201
0.0%
N/C
20.0%
N/C
Frequency
Mode 2
F207
V/I
N/C
RR
V/I
*Keypad
N/C = No Change — the setting remains as it was before setting parameter
F040
.
Note:
*Go to
F003
and/or
F004
and select EOI Keypad to use the
EOI for control.
F040
F040