ACE-tronics G9 ASD Installation and Operation Manual
95
Input Terminal 13 (LI5) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the LI5 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable LI5 terminal to any one
of the user-selectable functions listed in
Table 7 on pg. 236
.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for
additional information on the function of this terminal.
Direct Access Number — F123
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Input Terminal 14 (LI6) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the LI6 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable LI6 terminal to any one
of the user-selectable functions listed in
Table 7 on pg. 236
.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for
additional information on the function of this terminal.
Direct Access Number — F124
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No
Input Terminal 15 (LI7) Function
Program
Terminal
Input Terminals
This parameter is used to set the functionality of the LI7 discrete input terminal.
In addition, this input terminal must be specified as Normally Open or
Normally Closed.
This setting assigns the function of the programmable LI7 terminal to any one
of the user-selectable functions listed in
Table 7 on pg. 236
.
Note:
The Expansion IO Card Option 2 option board (P/N ETB004Z)
is required to use this terminal.
See the Expansion IO Card Option 2 Instruction Manual (P/N 58686) for
additional information on the function of this terminal.
Direct Access Number — F125
Parameter Type — Selection List
Factory Default — Unassigned
Changeable During Run — No