224
ACE-tronics G9 ASD Installation and Operation Manual
Monitor Output Function 11
Program
My Function
My Function Monitor
This parameter plays a role in the setup of the My Function feature by
establishing the function that is to be recorded and output as the Peak,
Minimum, or Normal (Avg.) value as selected at parameter Proportional.
Select the Monitor Display Input Setting number from
Table 12 on pg. 245
to
output the corresponding function.
Use the Communication Number if operating using communications.
Direct Access Number — F965
Parameter Type — Selection List
Factory Default — 2000
Changeable During Run — Yes
Monitor Output Function Command 11
Program
My Function
My Function Monitor
This parameter plays a role in the setup of the My Function feature by allowing
the user to select the Peak, Minimum, or Normal (Avg.) value of the
parameter
F965
selection to be recorded and output as a monitored function.
Settings:
Normal
Peak
Minimum
Direct Access Number — F966
Parameter Type — Selection List
Factory Default — Normal
Changeable During Run — Yes
Monitor Output Function 21
Program
My Function
My Function Monitor
This parameter plays a role in the setup of the My Function feature by
establishing the function that is to be recorded and output as the Peak,
Minimum, or Normal (Avg.) value as selected at parameter
F968
.
Select the Monitor Display Input Setting number from
Table 12 on pg. 245
to
output the corresponding function.
Use the Communication Number if operating using communications.
Direct Access Number — F967
Parameter Type — Selection List
Factory Default — 2000
Changeable During Run — Yes
Monitor Output Function Command 21
Program
My Function
My Function Monitor
This parameter plays a role in the setup of the My Function feature by allowing
the user to select the Peak, Minimum, or Normal (Avg.) value of the
parameter
F967
selection to be recorded and output as a monitored function.
Settings:
Normal
Peak
Minimum
Direct Access Number — F968
Parameter Type — Selection List
Factory Default — Normal
Changeable During Run — Yes
F965