ACE-tronics G9 ASD Installation and Operation Manual
Reset
Program
Utilities
Type Reset
This feature assists the user when performing fault analysis or by allowing a
quick system setup change when required. Performing a Type Reset results in
one of the following user-selected post-reset configurations.
Settings:
None
50 Hz Setting
60 Hz Setting
Reset to Factory Settings
Clear Past Trips
Clear Run Timer (Bearing Greaser)
Initialize Typeform
*Save User Settings
Restore User Settings
Clear Cumulative Fan Timer (FE79)
Accel/Decel Time Setting 0.01 – 600.0 Seconds
Accel/Decel Time Setting 0.1 – 6000.0 Seconds
Update EOI Firmware
Set EOI Memory to Default
Note: User settings that are stored in the memory of the EOI are not
saved via the Save User Settings selection.
Direct Access Number — F007
Parameter Type — Selection List
Factory Default — None
Changeable During Run — No
Forward/Reverse Run
Program
Fundamental
Standard Mode Selection
While operating in the Local mode, this parameter sets the direction of motor
rotation.
From the Frequency Command screen press the ESC key. At the subsequent
EOI Command screen select the Direction field and change the setting. Press
the Rotary Encoder and the new setting will be in effect.
This setting will not override parameter
F311
(Forward/Reverse Disable).
If either direction is disabled via parameter
F311
, the disabled direction will not
be recognized if commanded by the EOI. If both directions are disabled via
parameter
F311
, the direction command from the EOI will determine the
direction of the motor rotation.
Settings:
Forward
Reverse
Switchable F/R by EOI (Forward)
Switchable F/R by EOI (Reverse)
Direct Access Number — F008
Parameter Type — Selection List
Factory Default — Forward
Changeable During Run — Yes
Reset
F007
F008