108
ACE-tronics G9 ASD Installation and Operation Manual
V/I Input Point 1 Setting
Program
Frequency
Speed Reference Setpoints
This parameter is used to set the gain and bias of the isolated V/I input terminal
when the V/I terminal is used as the control input while operating in the Speed
Control mode or the Torque Control mode.
This parameter sets the V/I input level that is associated with the V/I Input
Point 1 Frequency (
F202
) setting when operating in the Speed control mode or
is associated with the V/I Input Point 1 Rate (
F205
) setting when operating in
the Torque Control mode.
Note: See note on
pg. 55
for additional information on the V/I
terminal.
V/I Input Speed Control Setup
Perform the following setup to allow the system to receive Speed control input
at the V/I input terminal:
• Set SW2 of the ACE G9-120V-PCB to Voltage or Current (see
Figure 8
on pg. 24
).
• Program
Fundamental
Standard Mode Selection
Frequency Mode
1
V/I.
• Program
Fundamental
Standard Mode Selection
Command Mode
Selection
Terminal Board.
Speed Control
Perform the following setup to allow the system to perform Speed control from
the V/I input terminal:
• Set V/I Input Point 1 Frequency (
F202
).
• Set V/I Input Point 1 Setting (
F201
) — the input analog signal level that
corresponds to the frequency setting at V/I Input Point 1 Frequency.
• Set V/I Input Point 2 Frequency (
F204
).
• Set V/I Input Point 2 Setting (
F203
) — the input analog signal level that
corresponds to the frequency setting at V/I Input Point 2 Frequency.
• Provide a Run command (F and/or R).
Once set, as the V/I input voltage or current changes, the output frequency of
the ASD will vary in accordance with the above settings.
This parameter value is entered as 0% to 100% of the V/I input signal range.
The V/I input is commonly used for a 4 – 20 mA current loop signal where
4 mA equals 20% of a 20 mA signal. Set this parameter to 20% for 4 – 20 mA
current loop signal applications.
Note:
When using the isolated V/I input terminal the IICC terminal
must be used as the return (negative) connection.
Direct Access Number — F201
Parameter Type — Numerical
Factory Default — 0
Changeable During Run — Yes
Minimum — 0
Maximum — 100
Units — %
Frequency Settings
/I
F201
F201
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]