PTC2 Thermal Selection
Program
Special
Special Parameters
PTC2 Thermal Selection
This parameter Enables/Disables the optional external thermal detection circuit
of the Expansion IO Card Option 2. A thermistor is connected from TH1+ to
TH1- of TB4 on the Expansion IO Card Option 2.
Should the thermistor resistance reading fall below 50
Ω
because of an over-
temperature condition or exceed 3000
Ω
because of an open circuit an External
Thermal Fault (OH2) will be incurred.
Note:
While this parameter is Enabled, the system cannot be restarted
until the thermistor value recovers to the level of 1.8k
Ω
from an
over-temperature condition. An Auto-Restart will not be
initiated subsequent to an External Thermal Trip (OH2). A
manual restart will be required in the event of an OH2 trip.
Settings:
Disabled
Detect Disconnect
Direct Access Number — F638
Parameter Type — Selection List
Factory Default — Disabled
Changeable During Run — No
Braking Resistance Overload Time (10x rated torque)
Program
Protection
Dynamic Braking
This parameter sets the time that the braking resistor is allowed to sustain and
overload condition before a trip is incurred.
This feature is useful for applications that have a fluctuating load or for loads
that require a long deceleration time.
Direct Access Number — F639
Parameter Type — Numerical
Factory Default — 5.0
Changeable During Run — No
Minimum — 0.1
Maximum — 600.0
Units — Seconds
Step-Out Detection Current Level
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact ACE World Companies Customer Support Center for information on
this parameter.
Direct Access Number — F640
Parameter Type — Numerical
Factory Default — 100
Changeable During Run — Yes
Minimum — 10
Maximum — 150
Units — % (or A; see
F701
setting)
Step-Out Detection Current Time
Program
Motor
PM Motor
This parameter is used with synchronous motor applications only.
Contact ACE World Companies Customer Support Center for information on
this parameter.
Direct Access Number — F641
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 25.0
Units — Seconds