ACE-tronics G9 ASD Installation and Operation Manual
23
Discrete Outputs
The form-A output contacts of OUT1 (A and C), OUT2 (A and C), and the form-C output contacts
BRAKE (A, B, and C) comprise the list of discrete output terminals. The output terminals are rated for
1 A/125 VAC.
All discrete output terminals are programmable and may be set to change state upon the occurrence of a
user-selected event.
10 VDC
PP is a 10 VDC/10 mA max. output for customer use.
24 VDC
P24 is a 24 VDC/200 mA max. output for customer use.
Communications
CN4 is the 2-Wire or 4-Wire serial communications port as selected by the setting of
SW1
.
See Program
Communications for more information on the requirements for setting up the ASD for
ASD-to-ASD communications and for ASD-to-host (i.e., PC, PLC, etc.) communications.
Alternate I/O Terminal Board
The ACE-tronics G9 ASD may also be controlled using the 24-Volt I/O Terminal Board (optional).
The 24-Volt I/O Terminal Board (P/N 3D658344_G901) control functions operate the same as the
120-Volt I/O Terminal Board with the exception that the discrete terminal activation is carried out using
a Sink or Source method of terminal activation.
In the Sink operating mode the CC terminal is connected to a discrete input terminal to activate the
assigned function — in the Source mode a 24 VDC signal is input to a discrete input terminal to
activate the assigned function.
There are no software changes required to use the 24-Volt I/O Terminal Board.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]