56
ACE-tronics G9 ASD Installation and Operation Manual
Past Trip 1
— This function records and displays the last trip incurred. Subsequent trips will replace
Past Trip 1. As trip records are replaced they are shifted to the next level of the Past Trip locations until
being deleted (i.e., Past Trip 1 is moved to Past Trip 2 and then to Past Trip 3 until being shifted out of Past
Trip 4). Once shifted out of Past Trip 4 the record is deleted. If no trips have occurred since the last reset,
None is displayed for each trip record.
Past Trip 2
— Past trip information or None.
Past Trip 3
— Past trip information or None.
Past Trip 4
— Past trip information or None.
Note:
An improper ASD setup may cause some trips — reset the ASD to the Factory Default
settings before pursuing a systemic malfunction (Program
Utilities
Type Reset
Reset to Factory Settings).
Direction
— Displays the Direction command (forward/reverse).
Discrete Input Terminals
— Displays the status (activated = reverse video) of the discrete input
terminals of the ACE G9-120V-PCB.
Discrete Output Terminals
— Displays the status (activated = reverse video) of the discrete output
lines of the ACE G9-120V-PCB.
Main Monitor Selections
Two (2)
Monitor Mode
items may be selected from the Main Monitor Selections screen to be displayed
on the Frequency Command screen while the ASD is running.
The selected items, along with their real-time values, are displayed on the Frequency Command screen
while running. Not all
Monitor Mode
items are available for display on the Frequency Command
screen. The available items are underlined on
pg. 54
and
pg. 55
.
Any two of the underlined items may be selected from the listing at Program
Utilities
Main
Monitor Selections. Select an item from the Monitor 1 listing and another item from the Monitor 2
listing to be displayed as shown in
Figure 22. on pg. 35
.
Past Trip 1
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]