ACE-tronics G9 ASD Installation and Operation Manual
237
32
33
Torque Limit Switching 1/Torque Limit Switching 2
— Activating combinations of discrete input terminals
Torque Limit Switching 1 and 2 allow for the selection of a torque limit switching profile as listed below.
34
35
36
37
PID Off
— Turns off PID control.
38
39
Pattern Operation Group 1
— Initiates the Pattern #1 Pattern Run.
40
41
Pattern Operation Group 2
— Initiates the Pattern #2 Pattern Run.
42
43
Pattern Operation Continuation
— Initiates a continuation of the last Pattern Run from its stopping point.
44
45
Pattern Operation Trigger
— Initiates the first Preset Speed of a Pattern Run and initiates each subsequent
enabled Preset Speed with continued activations.
46
47
External Overheat
— Causes an Overheat Trip (OH).
48
49
Local Priority
(Cancels Serial Priority) — Activation overrides all active serial control and returns the Command
and Frequency control to the settings of
F003
and
F004
for the duration of the activation.
50
51
Hold
(3-Wire Stop) — Decelerates the motor to a stop.
52
53
PID Differentiation/Integration Clear
— Clears the PID value.
54
55
PID Forward/Reverse Switching
— Toggles the gradient characteristic of the feedback response of the V/I
terminal during PID-controlled operation.
56
57
Forced Continuous Operation
— Ignore PID control settings for the duration of activation.
58
59
Specified Speed
Operation
— Runs speed as commanded by the Frequency Mode setting.
60
61
Dwell Signal
— Used in conjunction with the Acceleration/Deceleration Suspend function (
F349
) — suspends the
Accel/Decel function for the duration of the activation.
62
63
Power Failure Synchronized Signal —
Activates the Synchronized Accel/Decel function of the Regenerative
Power Ridethrough feature. See
F302
for additional information on this terminal setting.
64
65
My Function Run
— Activates the configured My Function feature. See
F977
for additional information on this
parameter.
66
67
Autotuning Signal
— Initiates the Autotune function. Set
F400
to Autotuning by Input Terminal Signal.
68
69
Speed Gain Switching
— Toggles the ASD operating mode from and to Speed Control and Torque Control.
Speed Control operation references parameter settings
F460
and
F461
. Torque Control operation references
parameter settings
F462
and
F463
.
70
71
Servo Lock
— Holds the motor at 0 Hz until a Run command is received.
72
73
Simple Positioning
— While operating in the Positioning Control mode, activation initiates the Stop command.
See
F381
for additional information on this terminal setting.
74
75
kWH Display Clear
— Clears the kWH meter display.
76
77
Trace Back Trigger
— Initiates the data Read/Store function of the Trace Selection parameter. See
F740
for
additional information on this feature.
78
79
Express-Speed Disable
— Terminates the Express Speed operation.
Note: NO/NC = Normally Open/Normally Closed. Selection numbers are used when selecting using communications.
Table 7. (Continued) Discrete Input Terminal Assignment Selections and Descriptions.
Sel. No.
Terminal Selection Descriptions
NO NC
Torque Limit
Switching Terminal
Torque Limit Selection
#1
#2
0
0
1
0
1
2
1
0
3
1
1
4
1=Terminal Activated
The 1–4 settings of the torque limit switching
selections are performed at parameters
F440
–
F449
.