ACE-tronics G9 ASD Installation and Operation Manual
247
Table 13. My Function Operator Selections.
My Function Computational Selections
Input
Function
Command
Function Name
Function Description
0
NOP (No Operation)
Disables the My Function feature.
1
ST
Execute data read/transfer.
2
STN
Execute inverted data read/transfer.
3
AND
Logical product of A AND B.
4
ANDN
Logical product of A AND B.
5
OR
Logical sum of A OR B.
6
ORN
Logical sum of A OR B.
7
EQ
Compares data — Outputs 1 if Equal; 0 if not Equal.
8
NE
Compares data — Outputs 0 if Equal; 1 if not Equal.
9
GT
Compares data — Outputs 1 if A>B; 0 if A
≤
B.
10
GE
Compares data — Outputs 1 if A
≥
B; 0 if A
<
B.
11
LT
Compares data — Outputs 1 if A
<
B; 0 if A
≥
B.
12
LE
Compares data — Outputs 1 if A
≤
B; 0 if A>B.
13
ASUB
Outputs absolute difference between A and B — |A–B|.
14
ON (Timer)
Enables the On response time delay settings of My Function Time Data 1 – 5
(
F928
–
F932
) for My Function Data.
15
Off (Timer)
Enables the Off response time delay settings of My Function Time Data 1 – 5
(
F928
–
F932
) for My Function Data.
16
COUNT1 (Timer)
Outputs a 1 upon reaching the pulse count setting of
F933
.
17
COUNT2 (Timer)
Outputs a 1 upon reaching the pulse count setting of
F934
.
18
HOLD
Outputs the peak output value since powering up or since the last reset.
19
SET
Sets data.
20
RESET
Resets data.
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]