ACE-tronics G9 ASD Installation and Operation Manual
139
Number of Times to Retry
Program
Protection
Retry/Restart
After a trip has occurred, this parameter sets the number of times that an
automatic system restart is attempted for a qualified trip.
The trip conditions listed below will not initiate the automatic Retry/Restart
function:
•
Input Phase Loss (Input Phase Failure)
•
Output Phase Loss (Output Phase Failure)
•
Output Current Protection Fault
•
Output Current Detector Error
•
Load Side Over-Current at Start
•
Earth Fault (Ground Fault)
•
Over-Current During Acceleration
•
Arm Over-Current at Start-Up
•
DBR Resistor Over-Current
•
Low-Current
•
Voltage Drop In Main Circuit
•
EEPROM Data Fault (EEPROM Fault)
•
Flash Memory/Gate Array/RAM-ROM Fault
•
CPU Fault
•
Emergency Off (EMG)
•
Communication Error
•
Option Fault
•
Sink/Source Setting Error (not used with the ACE-tronics G9 ASD)
•
Over-Speed Error
•
Over-Torque
•
Key Error
•
External Thermal Error
•
Externally-Controlled Interrupt
See the section titled
System Setup Requirements on pg. 8
for additional
information on this setting.
Direct Access Number — F303
Parameter Type — Numerical
Factory Default — 00
Changeable During Run — Yes
Minimum — 00
Maximum — 10
F303
F303
Buy: www.ValinOnline.com | Phone 844-385-3099 | Email: [email protected]