Jump Frequency 1 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 1 (see
F270
).
Direct Access Number — F271
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.00
Units — Hz
Jump Frequency 2
Program
Special
Jump Frequencies
Same as Jump Frequency 1 (
F270
) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at
F273
). When multiple
jump frequencies overlap, the system will recognize the lowest and the highest
frequencies as one jump range.
Direct Access Number — F272
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
Jump Frequency 2 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 2
(
F272
).
Direct Access Number — F273
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
Jump Frequency 3
Program
Special
Jump Frequencies
Same as Jump Frequency 1 (
F270
) and is used when multiple frequencies are
to be jumped (see the plus-or-minus value setting at
F275
).
When multiple jump frequencies overlap, the system will recognize the lowest
and the highest frequencies as one jump range.
Direct Access Number — F274
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — Max. Freq. (
F011
)
Units — Hz
Jump Frequency 3 Bandwidth
Program
Special
Jump Frequencies
This parameter establishes a plus-or-minus value for Jump Frequency 3
(
F274
).
Direct Access Number — F275
Parameter Type — Numerical
Factory Default — 0.00
Changeable During Run — Yes
Minimum — 0.00
Maximum — 30.0
Units — Hz
F271
F275